PV2-12

PV 12-12 metal-clad withdrawable switchgear is GE's OEM panel series, suitable for 3Phase AC  50Hz / 60Hz, 3.6 ~ 12kV single phase busway and single phase busway section power system. Apply to distribute power and implement system control, protection, supervision monitoring.

Item Unit Value
Rated Voltage kV 3.6, 7.2, 12
Rated Insulation Level Rated Power Fequency withstand Voltage (1 min) kV 42
Lightning Impulse withstand Voltage (Peak) 75
Rated Frequency Hz 50
Main Busbar Rated Current A 630, 1250, 1600, 2000, 2500, 3150, 4000
Branch Busbar Rated Current A 630, 1250, 1600, 2000, 2500, 3150, 4000(air cool)
Rated Short Duration withstand Current (4s) kA 25, 31.5, 40
Rated Peak withstand Current kA 63, 80, 100 (125)